Managing Compressed
Air Energy
Part III: Usage
Effects on Demand
By R. Scot Foss, Plant Air Technology
Eleven factors that affect a system’s
energy requirements.
Energy management in compressed air
systems can be divided into two sectors: demand side and supply side.
Once the energy constituents of demand in the system have been
determined we must determine how effectively we are using energy to
support the usage. In most systems, much of the demand usage is a
constituent of the supply energy.
There are a number of ways that energy
is consumed in an industrial air system besides the obvious. Some of
these are very interactive and difficult to isolate, but they must be
addressed in a typical plant compressed air system. Remember that air
systems are extremely dynamic.
In auditing most systems, there is a
common problem that always surfaces in the supply side of the system.
The issue is ownership. Responsibility in the system is broken up
between supply and demand, often with no one responsible for the demand
side of the system. Preventive maintenance normally is performed by
maintenance personnel. Overhaul and annual maintenance often is
contracted to compressed air service organizations. It is assumed that
these personnel are adjusting the equipment for its efficient operation.
Often, this is not the case. The following problems are typical.
Problem:
|
A service contract is issued with no
discussion or understanding of the objectives of the owner.
|
|
Preventive Action: |
Establish service objectives.
|
| |
|
Problem:
|
The owner, out of a lack of
knowledge, assumes that the right things will be done. Neither
party understands that the way the system operates must be owned by
someone. |
|
Preventive action: |
Designate a compressed air system
manager. |
| |
|
Problem:
|
The equipment is adjusted to
factory-recommended set points and signals when it is installed.
This has nothing to do with either how the system will work or
efficient operations. In most cases the equipment is never
readjusted for its useful life unless the controls are replaced.
|
|
Preventive action:
|
Periodically audit system
performance and adjust set points as needed. |
| |
|
Problem:
|
No one, including the service vendor
and the operators, has any records of how the equipment was
originally adjusted. No discussion occurred about how the system
should work, other than meeting a minimum acceptable pressure.
|
|
Preventive action:
|
Document system history. |
| |
|
Problem:
|
"Keep the equipment running" is a
vague protocol that assures energy waste and high operating cost. |
Preventive action:
|
Establish a rational approach to
system management that can allow unused equipment to be taken off
line and adjust signals, set points, and control philosophy
accordingly. |
These preventive measures must be
revisited each time demand changes or a piece of supply equipment is
added, deleted, or replaced, and the operating approach adjusted
appropriately. If not, the system energy efficiency and system
effectiveness will suffer.
The following 11 items are issues that
affect supply energy in the typical system.
1. Demand
Usage:
Demand usage is
the amount of energy necessary to support consumption assuming no
inefficiency in the system. Factors affecting demand were discussed in
previous articles.
2. Temperature
and Relative Humidity of Intake Air:
Using standard
conditions as a normalized value, higher temperatures at the inlet of a
compressor provide less dense air and result in less compressed air
mass. Because the compressor produces less results in terms of mass or
work energy, more energy is required to produce the identical results
systemically achieved at lower temperatures. Dynamic and positive
displacement compressors respond differently, but the systemic results
are comparable. When the inlet air represented is based on volume with
no regard to density, one can easily overlook this issue and the
corresponding energy required.
When the
temperature drops, the air is denser and the compressors will produce
more mass to the system using more energy. As work energy in the system
is our objective, inlet density or mass is a necessary component of
determining the power required and the number of compressors to support
all conditions relative to the system. At 0 F without the effect of
relative humidity, you will produce close to 12 percent more air by mass
and an equivalent amount of energy than at standard conditions. At 100
F without the effect of relative humidity, you will produce at least 7
percent less air by mass and an equivalent amount of energy.
Higher relative
humidity implies that there is more water present in the air at the
compressor intake. Because water does not compress, it reduces the
amount of net air that can be compressed. Relative humidity can
influence the net result by as much as 3.5 percent less displaced mass.
When effects of
temperature and relative humidity are combined, there can be as much as
a 22.5 percent swing in performance on the compressors in the system
from 0 F at 1 percent relative humidity to 100 F at 100 percent relative
humidity.
When you compare
the demand requirements including trim and conditional loads against the
inlet condition profile, the amount of energy needed will be a function
of the size of the compressors used. The larger the compressors as a
percentage of the total requirement, the more part loaded a large unit
will be depending on conditions and load. The smaller the compressors
are, as a percentage of the total requirement, the less part loaded any
one compressor can be. When properly controlled, the arrangement and
size of the units vs. the needs profile can represent as much as 33
percent less power systemically at the lowest temperature and load.
3. Compressor
Optimization:
The primary
objective of compressed air system management is to get the most mass
per kilowatt of electricity. The more mass you can achieve in any one
compressor in the system, the fewer compressors you will need to
accomplish the same results. Throughout this article, mass refers to
pounds mass (volume at density).
On positive
displacement compressors, the volume is fixed within the operating
pressure of the compressor. As you elevate the pressure within this
range, the volume will remain constant as the pressure and power
increases. This is an increase in mass. As you exceed optimum, the
mass will become constant and/or the motor efficiency will begin to
drop. The pressure and energy will increase, but the mass will remain
constant. In our experience, optimum will be achieved within a
compressor frame range at a higher pressure in the bottom of the frame
and at a lower pressure in the top of the frame. This is a result of
packaged losses that increase in the top of a frame.
On centrifugal or
other types of dynamic compressors, optimum is achieved in a slightly
different manner. There are zones on the performance curve. A portion
of the curve will produce constant mass. This implies that as the
pressure rises and falls the volume will change inversely and maintain
the amount of mass.
Above and below
this zone of performance, either the pressure will drop faster than the
increase in volume or the volume will diminish faster than the rise in
pressure. Both of these zones will produce less mass. The power does
not diminish as quickly as the mass in these zones. You would have to
determine at what pressure you would displace the most mass per kilowatt
of electricity by carefully examining the curve of the compressor at the
typical and extreme inlet conditions of intended operation.
The confusing
issue with centrifugal and dynamic compressors is that the performance
curve moves with changes in inlet temperature. It will drop and move to
the left as the inlet temperature increases, and rise and move to the
right as the inlet temperature drops. This would require adjusting the
operating pressure and the current limit adjustments on temperature
change to stay within this optimum range. If the curve is generous
enough for your conditions, you may be able to operate at relatively
little performance change despite conditions.
The number of
stages and the design will determine at what range of pressure this can
be achieved. Optimum is normally achieved at the lowest pressure in the
constant mass zone of the curve, which uses the least amount of input
power for the mass achieved. We have found that factory-supplied curves
only show performance between maximum stable flow and the surge pressure
of the unit. More than half of the compressors of this type that we
evaluate are operating at least a portion of the year below the pressure
and temperature where you will find maximum stable flow (not mass).
If you continue
down the curve from this point, the volume will become constant as the
pressure drops and the energy either remains constant or diminishes.
This is referred to as the choke zone. In the choke zone, you lose the
advantages of this type of compressor. Further down the curve the
volume will diminish as the pressure drops. This more-than-linear loss
of mass is called stonewall where you will achieve sonic velocity
through the unit.
Neither the choke
zone or stonewall are shown on factory-supplied charts. We would
suppose that this is not shown because you should not operate in this
manner. Nevertheless, we frequently find compressors that have set
points of operation below maximum stable flow and well below optimum.
We also seldom find compressors operating on the curve. Most of the
time they are operating in modulation or throttle. If the curve were
extremely vertical, where there is very little volume turndown on the
curve, you would have to operate at a low relative pressure in throttle
to prevent surge. It should be obvious that examining the curves in
terms of mass at pressure including minimum stable mass at various
pressures and inlet conditions is the only way to determine the best
operating set points for efficient performance.
You also should
request that the curves show throttled performance at pressure and power
at these various pressures and inlet conditions. Despite this need, we
did not encounter one facility in the past 250 audits that had enough
information to determine the best way of operating the compressor. In
fact, most owner/operators have never seen curves, even during the
selection process. Since this information is obviously needed and has
never been produced, one must be curious how factory required service
technicians adjust the units in the field. Our experience is that
keeping them running is the approach taken, not optimization. Factories
need to train their service personnel and the operators in performance
optimization of both the individual equipment and the system using
actual performance data and curves rather than typical factory set up
suggestions.
4. Compressor
Cooling Temperature:
All compressor performance is influenced
to some extent by the temperature at which the unit is cooled. There is
a considerable difference in types of compressors. The displacement can
be influenced by 0.5 percent to 3.5 percent of rated capacity for every
10 deg F increase over rated cooling media temperature. The inherent
inefficiency, combined with the range of cooling media temperature and
the maintenance condition of the coolers on the compressor, can effect
the displacement efficiency by as much as 25 percent on the most
temperature-sensitive types of compressors. Centrifugal compressors
should be tested for natural surge and throttle surge at least twice a
year to determine the performance decay of the unit as a result of
cooler fouling.
You must record the inlet conditions
during these tests so you can compare actual performance against
theoretical performance for these conditions. Factory service personnel
should either teach operating personnel how to perform these tests or
provide this test data to maintenance personnel on a regular basis if
you wish to minimize onboard energy and perform maintenance as required.
5. Systems
Storage vs. Rate of Flow of the Largest Event in the System vs. Loading
Time Required for the Next Available Compressor:
The more storage
capacity in the system, the less the pressure will fluctuate on any
demand event. This will allow you to maintain all of the compressors
that need to be operating closer to optimum. The slower the speed that
it takes to turn on the motor and load the next compressor, the more the
pressure will drop. You should be able to add trim compressors to the
system with a minimum delay and pressure drop. When this process
doesn’t work well, and the pressure fluctuates too much, the normal
reaction is to put all compressors in modulation and keep them on line
regardless of demand. This will avoid the fluctuation or pressure
decay, but not without a considerable increase in energy and operating
cost.
Another anomaly is
that as demand increases, the supply pressure drops. When the pressure
drops on all of the compressors that are base loaded, there is a loss of
isothermal efficiency proportional to the decay in the density of the
compressed air. In most systems, as the demand increases and you require
more mass, the compressors that are operating produce less mass. This
causes the pressure to drop exponentially. As you need more, you can
become less efficient with pressure decaying at an accelerated rate.
Careful design of
control storage and thoughtful selection of set points, signal
locations, and operating logic is necessary to achieve any relative
efficiency from the system. Single set point, rate of change automation
is the best approach to maintaining optimum system performance.
6. Resistance
to Flow in the System’s Piping and Downstream Point of Use Components:
The highest point of use pressure
requirement is determined by the highest article or inlet pressure on
the air-using equipment plus the highest installation differential
across the point of use transmission components such as filters,
regulators, lubricators, disconnects, hose, and fittings.
Original equipment
manufacturers install smaller transmission components with high
differential pressures to control manufacturing costs. The user of the
equipment must compensate by providing high initial pressures from the
plant air system. The tradeoff between high operating costs and the
price of equipment with lower operating pressures or differentials is an
important but rarely considered issue. Typical pressure drops across
accessories on air-using equipment have increased substantially in the
past 15 years. As long as this is a non-issue among the purchasers of
this equipment, you may be assured that manufacturers will continue to
use differential pressure as a tool for controlling manufacturing costs.
The highest
differential is achieved at the highest flow, highest inlet temperature,
and the lowest pressure. All specifications should incorporate this
information in performance queries and specifications with maximum
differential being the desired response. Compressor manufacturers
report that elevating the pressure 1 psig will increase power by 0.5
percent of the total connected onboard energy. If you are operating
with the compressors in load-no load mode and the elevation of pressure
does not increase the demand in the system, then this is true.
Unfortunately, most systems are in
modulation and do not have a demand control or expander. The elevated
pressure then will cause demand to increase. The demand increase will
be a function of the percentage of unregulated demand including leaks
and points of use with regulators adjusted to the maximum setting. The
power will increase proportional to the pressure increase adjusted for
the percentage of unregulated demand plus the 0.5 percent per 1 psig
rise. If the increased demand does not require an added compressor, the
influence on energy will be between 0.5 percent to 1.575 percent of the
total connected brake horsepower (bhp) from 100 percent regulation at
the point of use and no leaks in the system, to 0 percent regulation
plus leaks respectively per 1 psig rise in operating pressure.
If you are in modulation, and must add
another compressor in order to increase the pressure, the new compressor
will support a portion of the added load, but the total volume will be
shared across all modulating compressors. This can be so inefficient,
depending on the degree of part load prior to the add, that the effect
of a pressure increase can be 25 percent or more for a 1 psig pressure
increase if another compressor must be added. We haven’t seen a system
without leaks, nor 100 percent regulated below the lowest compression
pressure. Compressor manufacturers do not field test how their units
are influenced in systems, only packaged results. So much for the 0.5
percent per psig of pressure rise.
7. Differential
Pressure Across Supply Components Downstream of the Compressor Control
Signal Location:
Differential
pressure influences system energy in the same manner as in item 6.
Filters that degrade will cause the downstream pressure to drop.
Typical of these components would be aftercoolers, separators, filters,
and dryers when the compressor signal is located upstream of the
aftercooler. Specified performance never includes the influence of
differential. This must be determined at the highest flow, lowest
pressure, and highest temperature as with point of use equipment. What
is unique is that the differential will ride on the system’s pressure
and drive backwards into the compressor’s operating pressure signal.
If the operating
philosophy is to turn on compressors to maintain a system pressure of
100 psig, the pressure drop across the clean-up equipment will drive the
control signal up accordingly. If the clean up differential pressure is
10 psig, the signal pressure would have to be maintained at 110 psig to
maintain a system pressure of 100 psig. As you need more air, the
differential will increase at a higher rate of rise than the dropping
system’s pressure.
The more you need,
the harder it will become to satisfy the demand, and the more likely you
will turn on the next available compressor to share the load.
8. Higher
internal pressures resulting from differentials across components
upstream of the compressor control signal
This is
where the compressor control signal is downstream of all or some of the
components as in item 7. In this case, the differentials increase the
internal pressure in the compressor. In this case only, the compressor
energy will increase 0.5 percent of the total connected bhp per psig for
this internal pressure rise.
The same would be
true of an air to lubricant separator on a rotary screw compressor. As
the filter/separator dirt loads, the upstream internal pressure rises,
increasing the motor bhp. The separator is upstream of the control
signal. The increase in energy we are discussing is only true as long
as there is motor capacity available. Once you have consumed all of the
available energy, either the displacement will diminish, the motor will
overload depending on the compressor type, or you will have to add
another compressor. The differential and the energy will rise and fall
with the change in the compressor volume, but the system will not see
the effect of this, only the drive motor.
9. Resistance
to flow on inlet filters and their effect on reduced inlet pressure to
the compressors
As the inlet
filter becomes loaded with dirt, the dry inlet throat pressure drops
proportionately. If the compressor is not fully loaded, it will
increase in load to achieve the desired result as a consequence of the
controls set point at the reduced inlet pressure. The effect will be
different depending on how the compressor is operating.
In load-no load
mode, the increase will be in more load time. The energy increase will
be proportional to the ratio of the atmospheric pressure divided by the
added differential. This particular differential is measured in inches
of water and needs to be corrected to pounds/sq in. for the ratio (27
in. static pressure water gauge equals 1 psi).
If the compressor
is in modulation, the effect on energy can be more or less than linear
depending on the load on the compressor at the time that the inlet
pressure reduction occurs. Power is anything but linear in modulation.
Based on manufacturers’ recommendations for filter changes, most systems
will increase power by 2.3 percent to 3 percent during the time between
when the inlet filter is clean and when it is sufficiently dirty to
require change. If this causes the need for another compressor, the
influence increases the power dramatically.
10.
Inefficiencies resulting from how the
compressor controls are set up and their effect on unit performance
The effect of improperly set controls
can increase energy consumption by a modest amount to as much as 33
percent of the total connected kilowatts. A system control setting is a
very complex matter requiring a great deal of understanding. Previous
discussion outlined the general effects of the demand system and the
supply components on energy usage. This actual influence is specific to
the interrelationship between the compressors, their signals, set
points, and differentials within the system. This complex subject is
outside the scope of this article but is covered fully in a 90-page
section of the author’s "Compressed Air Systems Solution Series.
11.
Fouling of internal components on the air path
of the compressor
Fouling of internal compressor
components is specific to dynamic compressors such as centrifugal and
axial types. The dirt and condensibles from the inlet loading on
impellers and diffusers can cause considerable performance losses. As
this occurs, the surge pressure usually drops in the compressors.
Natural surge testing can assist in determining whether this condition
exists. You can also observe whether the unit is performing in terms of
mass at pressure and power comparing test results against rated
performance on its curve.
Measuring and Managing Energy:
For the most part, compressors have no
power monitoring equipment on them. In the infrequent case where there
is, the compressor is monitored with an amp meter measuring current to
the motor. Current is not an accurate means of monitoring power on a
compressor because of the relationship between mass and input power.
Monitoring and
trending total and individual input power is perhaps the best means of
trending operating cost and predictive maintenance issues. The only
accurate method we have observed is using kilowatts, relative to full
and part load performance.
Compressors and
systems do not usually fail. They degrade. If you trend individual
compressor input power vs. status and system efficiency, you can easily
avoid an interruption without the extravagant application of power as an
alternative. You need to monitor the total mass at pressure on the
demand side of the system and trend the demand mass divided by the total
input kilowatts.
Although many of
the individual compressed air energy issues have been understood for
some time, it has only been in the past five or six years that the
interrelationship of a system’s supply and demand has begun to be
understood. The improvement in and quality of information applied and
trended systemically has provided the best basis for separating the
theoretical from the actual. The commercial emphasis in compressed air
has always been with the equipment. Much more emphasis must be placed
on systems and their operations at all levels including system
operations, production usage, sales engineering, contract field service,
and equipment manufacturing.
The remarkable
opportunities available for operating cost reduction and quality
improvements in production are a strong indication that there is much
work that needs to be done in this area of plant asset management. Many
of the poor decisions that are made are out of fear of not satisfying
production. Fear is only present in the absence of knowledge.
Education, ownership, and the application of information are the
beginning of more effective plant air systems.
Reprinted
with permission from R. Scot Foss, president of Plant Air Technology,
Charlotte, N.C., a company specializing in system auditing and design. This
article is based on his book, "Compressed Air System Solution."
A
portion of the proceeds from sales of the book is donated to children’s
charities. To order a
copy of the book, please
contact Southern Corporation. |