|
Improving
Air
System
Efficiency
by: R. Scot Foss, Plant Air
Technology
Part 7: A closer look at the demand side of compressed-air systems
It often seems that
compressed-air system performance is evaluated only from the perspective
of the supply equipment. If pressure anywhere in the system is below
whatever is believed to be the minimum acceptable level, the common
diagnosis is "insufficient supply." Little more is done to evaluate what
is going on in the system. In existing systems, demand usually is
calculated by adding up the rated capacity of all the compressors that
are on, regardless of how much power they are pulling. Users do not
realize that an on compressor is only an indication of cost -- not an
indication of need!
Without demand,
there is no requirement for supply. Most compressed-air systems have
little or no storage and an uncontrolled approach towards expanding the
air to the various pressures at which it will be used. Compressor
manufacturers have developed formulas and perceptions based on the
assumption that all of the demand is managed. In reality, less than half
of the air (by volume), which is consumed is regulated, and half of the
regulators in use are adjusted to their wide-open position. Typically,
80% of total demand is unregulated. As real demand increases, supply
pressure drops and 80% of the total use volume diminishes proportionally
to the reduced density of the supply air. The inverse is also true.
Demand in
compressed-air systems can be viewed as many holes through which air
flows and expands to do work. The number of holes, whether they are open
or closed, how fast they open and close, the coincidence of these
occurrences, and the various operating pressures determine the demand in
the system. Following are the categories of usage:
Appropriate production usage:
This term can be
applied to usage for which the compressed-air system was installed in
the first place. Some examples of appropriate usage would be valves,
cylinders, instruments, air motors, pneumatic hand tools, and, in some
cases, blowing applications. A portion of the total appropriate uses
necessary to production will be regulated, while the balance will be
unregulated. These applications are appropriate for compressed-air usage
even if not properly controlled.
Inappropriate production usage:
These are
applications that could be accomplished better with electricity,
hydraulics, or mechanical power instead of compressed air. Examples
include use of plant air for aspiration of a flue gas, agitation or
oxygenation of liquids, or aeration. These applications should be
serviced with a single-stage, low pressure blower. When plant air is
used instead, there is seldom an understanding of cost or consequences.
Sometimes it is simply an effort to avoid the purchase of alternative
non-air-using equipment to produce the same functional result. Certainly
one would not install a 3Ú8-in. air hose to blow air with an annual
operating cost of $18,000 when a 1-hp blower could do the same thing
with an installed cost of $400 and an operating cost of $850 per year.
Leaks:
Leaks represent
waste, which is internal to the production equipment as well as in the
general piping system from the compressors to the points of use. Leakage
noise can range from inaudible to extremely irritating.
Remember that most
leaks start small and then grow. It is not unusual for the sum of all
leaks to equal up to one-third of the total air usage if they are not
brought under control. The best way to evaluate leakage problems is to
monitor the demand flow, corrected for pressure and temperature.
Artificial demand -- This is the excess volume of air that is created on
unregulated users as a result of supplying higher line pressure than
necessary for the applications. It includes leaks, drain valves, and
blowoff. When the supply pressure fluctuates, artificial demand
increases and decreases from a minimum to a maximum waste level. As real
production demand decreases and the pressure rises, artificial demand
increases. Repairing leaks in the system causes pressure to rise and all
unregulated demand (including the balance of the leaks) increases
proportionately to the pressure rise.
Because little care
is used in selecting regulators and filters, they frequently have high
pressure drops. Operators will increase the pilot pressure to improve
the workability of their equipment to solve application problems. When
operators no longer can elevate the pressure, they run into the supply
pressure of the system. At this point the application will track the
supply pressure. The increased volume created is artificial demand,
which can represent between 10 and 25% of the total air used.
Expander Offers Solution:
A demand expander
can correct this problem when adjusted to the system's minimum required
pressure. An expander is a main line control valve (or valves) that
controls the maximum pressure at which demand air can be removed from
the system. Unlike a regulator, which restricts flow to control
pressure, an expander increases the volume from the higher upstream
pressure to the control pressure. Because expanders are sized for the
expanded flow at the lowest operating pressure, they impose an almost
immeasurable resistance to flow on the system. They require very little
supply energy to function properly. Compare this to a regulator which
can require 5 to 10% of the system's input energy to overcome resistance
to flow.
Expanders also are
very precise control devices, normally using a PLC platform-centered,
PID control format. The expander has a control and response sensitivity
within tenths of a psi. The use of an expander allows storage to be
maintained in the upstream supply system to handle variations in demand
rather than using "on board" power.
Another problem in
the system provokes operating at elevated pressures. If the system is
operating correctly, and demand is stable, a neutral (or 0 cfm) rate of
change occurs. This implies that supply energy and demand energy are
equal. When more air-using equipment comes online, this is referred to
as a demand event. The excess demand over the supply energy is expressed
as a negative rate of change. Until the supply system responds to the
event, the air required is taken from the demand piping system, causing
the pressure to drop. This pressure decay will be greater at the point
of use and diminish closer to the supply. The decay will continue
systemwide until supply adjusts; then the system will assume a positive
rate of change until the air removed from the system is replaced,
pressure is brought back to the original control point, and rate of
change returns to neutral.
Open
blowing:
Open blowing is
plant air used for moving product, drying, wiping, cooling, and parts
and scrap ejection. These applications typically are little more than
copper tubes or pipe nipples attached to rubber hose or polyvinyl
tubing. Although regulation should occur, these applications seldom have
regulators installed. Depending on the shape and configuration, a
1Ú4-in. copper tube can pass 48 to 108 cfm at 70 to 100 psig. This
represents 13 to 30 bhp of supply energy. At $0.06 per kW-hr, plus
maintenance and depreciation, compressed air costs about $2.00 per 100
cfm per hr of usage. That means the 1Ú4-in. copper tube used for open
blowing could cost between $4037 and $18,922 per year on a 3- shift
basis. The people who randomly apply these nozzles do not know the
financial implications of their action, or what alternatives are
available.
Open
Drainage:
This occurs when
plant air is released through open valves, notched ball valves, and
motorized or solenoid-operated drain valves to dispose of compressed air
effluent, such as water and/or lubricant. Although these seem like a
positive means of effluent removal, the consequences can be expensive.
The usage is not usually significant by volume, but the high rates of
flow for short periods of time can depress the supply pressure enough to
keep any compressor from unloading or turning off. Let's investigate the
use of five timer-operated, motorized, 1Ú2-in. ball valves to drain
effluent from a small system. If left open, each valve will exhaust 477
ft3 of air at 100 psig in one minute. If the timers are set
for 5-sec drain cycles, each valve will consume: 477 x (5/60) = 39.75 ft3/cycle.
Assume that the
supply system has 60 ft3 of storage per psig, or 2169 gallons
of capacity for all tanks and piping. This implies that for every 20 ft3
of air removed from the system (above the amount that is being put into
the system), the pressure will drop 1 psig. Every time one drain valve
opens and dumps 39.75 ft3 of air for five seconds, the system
pressure drops 2 psig.
If all of the timers
are set for 5 sec of draining every five minutes, the statistical
probability of coincidental drain events would be quite high, at least
for up to three valves. If three valves actuated simultaneously, the
supply pressure would drop 6 psig. Because one or more drains are open
at least 8.33% of the time, pressure could not be kept high enough to
time out the motor on an off compressor before the pressure dropped to
reload the compressor. If all five units function simultaneously, which
will happen statistically, the 5-sec flow seen by the compressor room
would be 198.75 ft3, which is a rate of flow of 2385 scfm.
This would be more than enough to load the next available compressor,
regardless of its size.
If you feel
compelled to use solenoid or motorized valves for drainage, adjust the
timer to the shortest possible duration and increase the frequency. This
not only will reduce the air flow per cycle but also the potential for
coincidental drainage events. The objective is to remove liquid, not
air.
Centrifugal compressor bleed bypass or
blow-off:
This is part of the
normal control functions of a centrifugal compressor. A substantial
portion of the cooling of the compressor is assigned to air being
compressed. There is a minimum flow required to prevent overheating.
When the demand for air in the system is below the minimum stable mass
flow for the type of compressor, the control system will blow off the
difference between the minimum stable flow and the actual demand
requirement to atmosphere.
Blowing off
compressed air to the atmosphere is an intentional waste of energy if
the total minimum stable flow capacity of the on-line centrifugal
compressors is more than the actual requirement. It is not uncommon for
all or some of the centrifugal compressors, which are on, to be blowing
off. This is not necessarily because the controls are not working
properly. It is common to oversize compressors.

Blow-off or bleed
bypass is real demand that requires energy, whether it is productive or
not. The objective in operating a centrifugal should be to keep each
base load unit fully loaded and operating on its natural curve on a
year-round basis. You can configure an arrangement of centrifugal-only
compressors that do not blow-off if the following occurs:
· demand is determined by correcting for mass flow at density to the
anticipated operating pressure, including the full range from maximum to
minimum and off production
·
supply capabilities are determined from actual curves at various inlet
conditions and operating control approaches to determine the best sizes
and fits for the range of demand required
·
actual limited throttle capabilities including field adjustments are
evaluated based on performance curves for the range of inlet conditions
at the anticipated operating pressure, and
· the
back-up compressor to support a unit failure is properly designed and
integrated into the configuration. This implies that the off compressor
is evaluated for the permissive start requirements from a hot start.
Control storage must be provided to limit the minimum acceptable
pressure drop that occurs while the compressor motor is being turned on
and the compressor goes through its permissives. It will then have to
close the blow-off valves and open the inlet throttle valve allowing the
capacity of the unit to stop the decay of pressure and replace the air
lost in control storage.
Attrition:
This is the
additional air consumption that occurs on applications that result from
unmanaged wear. Attrition typically is a normal function of sand or grit
blast nozzles, textile machinery nozzles, etc. Solid particulate in the
air stream will cause nozzle wear.
Unattended attrition
can increase a particular volumetric consumption by 50% and frequently
provokes the increase of pressure at both the point of use and the
supply. A 1Ú2-in. nozzle with 1Ú16-in. wear, which has had supply
pressure increased from 80 to 90 psig (to compensate for the wear), will
increase the volume by 50%. Monitoring attrition is essential. Blast
nozzle operators have calipers that can slide into the nozzle and
indicate an acceptable or unacceptable level of wear. Blast operators
know that excess wear spreads the pattern, reduces thrust or force per
square inch, inhibits desired quality, and impedes labor efficiency. On
stationary applications such as air jet looms or spinning machines, mass
flow at pressure should be measured regularly to monitor wear. The need
for a few more cubic feet of air on each of a few hundred production
machines can indicate the need for another compressor.
The logic behind any
attrition management program is benchmarking the mass flow at pressure
or measuring the actual wear on the nozzle. The nozzle or insert should
be changed when the cost of energy to maintain the wear exceeds the cost
of changing the nozzle or insert.
Purge
Air From Desiccant Dryers:
This air is consumed
in the process of stripping air dryers of moisture. The process can
range from 3 to 14.7% of the total air systems capacity from one method
of purging to another. There are specialty categories of air, such as
CDA 100, which is used for the microelectronics industry where purge can
approach 25% of total capacity for the system. This is primarily used
where the desired pressure dew point can be as low as -100° F.
The purge rate of
flow is a function of the capacity of the dryer and its purge pressure,
which normally is adjustable. An air reactivated or heatless dryer rated
at 3000 cfm at 100 psig has a purge flow of 441 cfm at 100 psig. If the
air flow through the dryer is 1000 cfm, the purge rate of flow will not
change. With dew point control, the total cycle time increases, but the
rate of flow will remain at 441 cfm for the preset purge time duration.
The time between purges will lengthen as the flow through the dryer
drops.
The rate of flow,
not the cycle time, affects the system and loads compressors. One might
have been led to believe that if the length of the cycle is doubled, the
amount of purge will be cut in half. The effect of loading or the peak
compressor requirement will not change; the same purge cycle will just
occur less frequently. This will reduce the kW/hr, but not the power of
demand.
Bleed
Air or Control Bypass:
This is a
point-of-use consumption where air is bled off the system or bypasses an
application as a means of improving the accuracy of pressure and/or flow
control. Where accuracy of pressure is important, and there is
considerably more power or higher pressure than needed on line, the
pressure can fluctuate erratically or perturbate. There is normally a
control or storage-associated problem that is compensated for, with
bleed or bypass control.
Constituents of Demand:
In general, the
previously discussed issues represent the constituents of demand
encountered in audited systems. The last four categories -- bleed air,
purge air, attrition, and bleed bypass -- only represent 23% of all
systems, while the others are typical constituents.
Other
Influences on Energy and Operation:
The amount of energy
required to operate the system not only is based on how much air is
consumed in demand, but also how it is used. The relationship between
the supply arrangement and the way demand is used, will also determine
the energy consumed. In examining demand the question must be asked,
"Why do we operate the system the way we do?" Breaking down the issue
provides the information necessary to manage the system most
efficiently.
Minimum load is the
condition with the least amount of energy requirement, but it usually
represents the most hours of operation per year in most systems. In
manufacturing, a daylight or on-production mentality is often developed.
From Friday night at 11 p.m. until Monday morning at 7 a.m. equals 56
hours of weekend compressed air service. With three shifts, eight hours
per shift, five days per week, the weekend represents the longest shift
or 31.8% of the total time (2812 hours per year). If this low load
condition also includes the third shift, the condition of usage can
represent as much as 4962 hours a year out of a possible 8760 hours. Low
or minimum load is usually not evaluated and winds up being the
stepchild when sizing the system and its equipment. During the minimum
load condition, there is usually a significant amount of partial load on
a larger-than-necessary compressor or compressors that are on and were
sized for the peak demand.
Low-load
requirements should be evaluated on their own for the best operating
mode. In many cases, this operating condition supports only auxiliary
requirements, such as heating, ventilating, and air conditioning
controls in the system; a dry sprinkler system; mixing motors that may
be operating around the clock; diaphragm pumps; instrument air; etc.
Although these may be legitimate usage, small isolated support might
make more sense rather than supporting the entire system. In many cases,
some users also could be better applied with electrical drive equipment.
Another poor use of
air during the minimum load condition is abandoned production air usage.
Operators turn off their electrical controls but do not close the air
valve on the machines when they leave their work stations. Up to
one-third of the low load condition has been found to be representative
of this usage. There needs to be specific management direction regarding
air usage shut off when a work station is abandoned. This can account
for as much as 5% of the annual operating cost of compressed air in the
plant.
If demand is managed
with a demand expander, pressure could be reduced considerably during
low load to control operating costs. The percentage of unregulated air
consumers' volume, including leaks, usually increases as the demand
diminishes and system pressure rises. This is particularly true when the
supply is poorly controlled and sized much larger than the low load
needs. If normal production is operated at 90 psig, the demand control
pressure could be reduced to between 55 and 70 psig on the low load
condition, depending on the equipment needs.
Even the most
diligent maintenance professional can easily overlook the opportunities
of minimum load. This is the place to begin auditing the air system. It
represents the start of determining the constituents of demand as well
as a significant opportunity for operating cost management.
Some
Facts About Air Leaks:
· they are insidious and will grow in time. Typical air line contaminants
are water vapor and oxides, which make an excellent lapping compound.
Passing these contaminants through normal leak annulars ensures wear. If
the system is controlled by pressure only, leaks will grow at a faster
rate than in a demand-limited or controlled system. If some leaks are
fixed -- and the demand pressure rises as a result -- the remaining
leakage volume will increase in direct proportion to the relative
increase in pressure. With this elevated velocity, the leaks will
increase in physical size until the increased volume causes the pressure
to drop to the original level of waste
· if
system waste is allowed to grow unattended, the demand will eventually
accommodate the supply that is on line until all compressors that are on
are fully loaded. As leaks rob work energy from the system, the mass
flow lost must be replaced if the pressure is going to be managed. The
replacement air brings in water vapor, acid gas, hydrocarbon vapor, and
other industrial contaminants that must be processed and removed. Most
systems with contamination problems can be fixed by controlling leaks
and other waste in the system
·
vapor seeks the lowest vapor pressure. This engineering anomaly can be
helped along when we have a combination of a high percentage of leaks
combined with desiccant or low-dew-point drying. If the ambient relative
humidity is also high, water vapor will diffuse into the system from the
atmosphere using the leaks as a vehicle. The higher the vapor pressure
differential, the more effective the molecular diffusion or jet pump
effect. Because leaks are neither planned nor managed, they increase
flow through components in the system. The increase in flow causes an
exponential increase in differential pressure across the components,
resulting in a drop in downstream pressure. At the point of use,
components are selected with little regard to differential. It is
commonplace to elevate the regulated pressure to correct application
workability. With this sloppy approach, leaks at the point of use have a
most profound effect on the system. Imagine the capital and operating
cost for installing another compressor at the supply end because of
nagging complaints of continuously dropping pressure at one or more
use-points. Sadly, leaks and plugged filters are usually the cause.
· leaks are the primary cause of problems with compressor control systems.
Unfortunately, service providers neither use ultrasonics or regularly
soap control lines to check for leaks. A few inaudible leaks can
false-load a compressor as though there is large downstream demand. The
result of this type of problem is severe cycling or hunting in the
modulating control mode, and
·
it
is nearly impossible and impractical to eliminate all leaks from a
system. Twenty percent of all leaks, by volume, are inaudible and very
small. By unit count, 70-80% of leaks fall into this inaudible category.
It is relatively easy to find and eliminate 75% of a system's total leak
volume. Beyond this level, it is difficult to justify the return on
labor invested even on a benchmarking basis. Most maintenance personnel
only fix audible leaks. Keep in mind that a leak would have to be very
large in order to be heard over typical industrial background noise.
How
Compressors are Oversized:
When the initial
sizing of a system is calculated, volumes at various pressures are added
with no correction for mass density. There also are generous fudge
factors for pressure and volume used at the various assessment stages of
sizing. As an example, a manufacturer of equipment measures his demand
at 100 cfm at 70 psig and then increases the pressure to 90 psig as a
fudge factor. He expresses the demand as 100 cfm at 90 psig. This
overstates the required mass flow at density. Percentages are
arbitrarily added to volume. Pressures are elevated to accommodate the
compressor specifications. Most of this is done to offset the unknowns
or the fact that last time this exercise was done, mistakes were made.
It is assumed generous oversizing will take care of the previous errors,
whatever they were. If we had to pick a percentage relative to common
oversizing, it would exceed one-third of the actual demand.
The turn-down or
throttling capabilities of a centrifugal compressor can range from 20%
to 40% of the total capabilities at the lowest operating inlet
temperature. As the inlet temperature rises, the throttling capacity
reduces, because the curve drops without the minimum stable flow
changing. This may be evaluated on a unit- by-unit basis when the
engineering evaluation occurs. Unfortunately, the effect on system
operation is not evaluated considering the total number of compressors
which will be operated versus the range of demand required. Most systems
are evaluated based on peak demand. They are seldom evaluated for
minimum demand or turn-down requirements.
All centrifugal
compressors have protective controls to ensure the compressor does not
operate at or below its minimum stable flow point. These are either
electrical minimum current (current limit low) or pneumatic blocks,
which cause the compressor to blow off. The correct means of adjusting
these limits or blocks is to perform a throttle surge test of the
compressor at a specific inlet temperature and relative humidity, and
operating pressure. By determining the input power at which the pressure
begins to rise on the throttle surge curve or line, you can compare this
to the rated performance of the compressor and interpolate what the
minimum stable mass flow is at operating pressure.
Once you perform the
test, you can adjust the blow-off controls to activate slightly before
this point on the throttle line. Curves are seldom supplied (or
requested) for compressors. The method that is used by the factory
service technicians is to set the limits generously enough so that none
of this needs to be done. The result is significant limits imposed on
the throttling capacity of the compressor. We commonly find the
compressor fields adjusted to blow off at 15-20% throttled off the full
load capacity of the machine at the coldest condition and 5-10% of the
full load capacity on the hottest summer day.
Because these units
are very permissive, they are relatively slow to load up from a motor
off and ready to start condition. The result is that most systems with
centrifugal compressors have one extra compressor on all the time. When
you evaluate the demand turndown and add another compressor to the
online supply to protect the system against a unit failure, this forces
all compressors to throttle. It is not uncommon to size a system to
operate with two or three centrifugal compressors to support the demand
in the system plus the extra on compressor to cover for a unit failure.
If the demand requirement is less than 2Ú3 of the total capacity of the
three compressors plus the extra unit online, you will have to blow off
one or more compressors. Unfortunately most evaluations attempt to
determine the type of compressor to acquire, when more than one type may
be the prudent choice. Mixed types of compressors seldom are applied to
any specific system. Other types of compressors, like
positive-displacement units, have less limited turndown capabilities and
can start from a cold off position within seconds. There is no need to
operate another base load compressor in the event of a unit failure.
Most evaluations begin by asking what type, size, and number of
compressors are needed for the system. The question might be better
asked: What types, sizes, and number of compressors will best suit the
range of demand and ambient conditions that will be seen?
Reprinted
with permission from R. Scot Foss, president of Plant Air Technology,
Charlotte, N.C., a company specializing in system auditing and design. This
article is based on his book, "Compressed Air System Solution."
A
portion of the proceeds from sales of the book is donated to children’s
charities. To order a
copy of the book, please
contact Southern Corporation.
|