|
Improving
Air
System
Efficiency
by: R. Scot Foss, Plant Air
Technology
Part 6: Understanding compressor
controls and working with them.
Your understanding
of compressor controls and how to use them can be an important factor in
how well your air system functions and the amount of energy it consumes.
Unfortunately, many systems consist of a series of individual unit
controls, with no provision for meeting the challenge of getting two or
more compressors to operate together efficiently. Once compressors are
purchased and installed, attention usually is limited to keeping the
machines running - but not necessarily efficiently. Unless the output
falls below the minimum acceptable pressure or the equipment fails for
one reason or another, the compressor's controls are ignored.
Back to
the Basics:
Remember,
compressors don't make pressure - they pump volume. If a compressor is
rated at a given pressure, that means it is constructed to safely
contain that pressure. The controls limit the pressure relative to the
configuration into which the compressor is pumping. If more volume is
pumped into the downstream system than is removed by the users, the
pressure rises. If more air volume is removed by users than is pumped
into the system, the pressure falls. The job of the controls is to limit
the pumped volume partially - or entirely - relative to the pressure set
points adjusted on the controls. At full load, the compressor pumps 100%
of its volumetric capacity and the controls perform no function.
Whether looking at
single or multiple compressors, it is important that each compressor
that is running should be optimized - this means pumping the optimum
volume at the optimum pressure, or the maximum pounds of gas per minute
at whatever pressure is accomplished with the least amount of energy.
In addition,
controls on compressors protect the equipment. They are usually
integrally tied to safety alerts, alarms, or shutdowns. It is to your
advantage to know what safety features are in the control system and how
they function.
The vast majority of
older compressors have few and relatively simple safety features -
sometimes only encompassing high pressure and temperature shutdowns.
Many newer compressors use microprocessors for controls and safety
functions. Their control consoles include many more safeties and complex
functions.
Control
Signals and Signal Location:
Regardless of the
type of control on the compressor, there must be a pressure signal to
operate the control. The location from which the signal originates is
critical to how the unit will function, how much energy it will consume,
whether it will function with other compressors, and whether the desired
performance will be achieved.
The idea behind
control signals is to take a pressure from a location inside or
downstream from the compressor and transmit it either pneumatically or
electronically to the compressor controller. This signal interfaces with
a pressure switch or transducer. In most compressors, the intent is to
move air from the compressor air end downstream, to keep the pressure at
the signal location at or between an adjustable set point (or set
points) preloaded in the compressor controller. There are a number of
potential locations for pressure signals that are designated by
compressor manufacturers, Figure 1.

Because the location
will change the amount of energy the compressor consumes and the
performance, the following should be noted:
· Compressor
manufacturers have rated their performance based on packaged volume,
pressure, and energy upstream of the aftercooler. Signal location is
normally not discussed in the product literature. In some cases,
performance is stated as "packaged," but this does not indicate what is
in the package or where the signal is located.
·
Some
manufacturers have used the A location for many years, but recently have
begun to use the B location
· Other
manufacturers state performance downstream of the aftercooler,
interpolating the Dp across the aftercooler in the
performance, even though the signal originates upstream of the
aftercooler, and
· Many
manufacturers use the same flow components in a package frame size to
accommodate many capacity sizes - up to twice the size at the top of the
frame as at the bottom of the frame. The effect of the components' Dp
and the signal location will have a dramatic influence on performance.
As the volume displaced in a given frame size increases, the Dp
increases as a square function of flow, and the performance decreases.
One of the problems
with installing the signal location upstream is that the quality of the
air there is poor. The air is saturated with moisture and can be laden
with lubricant. Both the water and lubricant will condense in the signal
line, fouling the controls or transducer. Another prevalent problem is
the effect of accumulating liquids in the control line - this can result
in too high a pressure signal. Taking the signal from downstream of the
aftercooler, at the separator, will reduce this problem by about 80%,
but will still only delay the inevitable. Some manufacturers install
signal line blow-outs, so that the lines can be kept clean on a daily
basis. However, most have no means of correcting this problem other than
disassembling the control lines or using a different signal from a dry,
clean source downstream of the clean-up equipment.
Set
Points and Dead Bands:
Compressor controls
limit performance and/or displacement volumetrically, normally based on
pressure. The controller will attempt to keep the signal pressure
between the set points or at the set point. The set points are normally
adjusted by the manufacturer's representative, and many operators and
plant engineers are unaware of how these controls are set.
Most compressors use
two set points. These represent the dead band of the unit controls. The
dead band is the differential pressure between the highest pressure at
which the compressor pumps the least mass of air and the lowest pressure
at which it pumps the most mass of air. These two set points also
normally represent the unload and load pressure. Adjusting the set
points has a significant effect on how the compressor operates. The
differential determines how the unit will respond to manage the pressure
at the signal location.

A typical set of
control points on a pressure switch is shown in Fig. 2. There is a
10-psig differential between the control set points. If the controls on
this compressor are set to modulate, this implies that each 1-psi
increment represents 10% of the capacity within the set points. It
should be noted that the volume is at pressure. As the displaced
capacity of the machine increases, the pressure will also drop. This
means that the work energy is increased less than linearly.
Different types of
compressors will respond in different ways. Rotary-screw compressors
will displace between 40% and 100% of capacity. Thus, in the dead band
modulating, 60% of the capacity can be displaced. If the unit were
modulating at 50% of the dead band (as indicated in Fig. 2), the
compressor would be putting out 50% of the top 60%, or 700 cfm at 113
psig. Just before reaching the unload point, the unit will throttle back
to 40%, or 400 cfm at 118 psig.

If the machine was
in the load-unload operation, Fig 3., it would displace its capacity at
variable pressures between the load and unload pressure. If the
compressor is a positive-displacement unit, the volume will remain
constant from the load to the unload pressure at a rising pressure -
therefore increasing density at rated mass or work energy available. In
the case of reciprocating compressors, some are multi-step. In a
two-step unit, the compressor will function at 0% and 100%, such as
dead band A in Fig. 3. Dead band B in Fig. 3 is a three-step control which
would displace 0%, 50%, and 100%. This would require either two pressure
switches or a control regulator to perform the same function as two
pressure switches. Most larger reciprocating compressors are capable of
at least three-step operation. Some manufacturers offer five-step
compressors, which displace 0%, 25%, 50%, 75%, and 100%.
If a unit would
achieve its optimum mass at a given pressure, setting the unit controls
below this point would achieve less than optimum performance. Setting
the controls above this point would overload the drive motor. Careful
planning of set points can determine how many compressors are necessary
to achieve a particular result.
Some compressors,
such as centrifugals, use a single set point controller. Most of these
types of controls either attempt to maintain the signal pressure at the
set point with modulating inlet and blow-off controls, or they operate
load-no load within an adjustable proportional band related to the set
point. The objective should be to keep the unit on a natural curve and
out of the limiting controls for this type of base load compressor. As
the signal pressure approaches the set points, the controls engage and
move the operation off the curve and into the limited control range on
the throttle line. In load-no load, the signal pressure rides the
natural curve of the compressor, Fig. 4.

When the demand
exceeds the capacity of a compressor, the pressure drops below the
lowest set point below the dead band. This condition is called the draw
down. This is an important condition to understand, because all
compressors that are base loaded on their own controls or with a
sequencer must be in draw-down before the next compressor becomes
loaded. Figure 5 demonstrates a cascade of three compressors with two
units in draw down.

If all of the
compressors in Figure 5 were in modulation and the demand reduced, the
signal pressure would rise and all compressors would throttle and remain
part loaded. If the dead band spreads for each machine had a different Dp,
the signal pressure that resulted would be a function of the way the set
points were adjusted.
Determining the best
differential pressure between the set points presents an interesting
problem. The wider the set points, the farther the system gets from
optimum performance. Many service people set the controls at 10 psid or
more to reduce potential cycling. The results are considerable pressure
fluctuation and poor performance. By increasing the differential, there
is less capacity per psig - which reduces the rate of response. Effectively using control storage will narrow the operating range of the
compressor or compressors. Managing the operating range closer to
optimum reduces the energy required without causing excessive cycling.
With centrifugal
compressors, the market has been attracted to the concept of holding a
single control pressure. For this to occur, the unit must be operated in
modulation.
There is a
misconception that this type of compressor does not need storage. While
there is a degree of truth to this statement, there are a few problems
associated with no capacity to store air and the use of single set point
modulation. One is the need to always have more compressor capacity on
line, either throttled or blowing off, so that negative event changes in
the system can be supported without a significant drop in pressure. On
the other hand, if a large demand event exits the system faster than the
response speed of the compressor control valves, the compressor can rise
to surge without adequate storage. Too frequently, the set point
adjustment is set low in modulation to compensate. The results can be
poor efficiency. Controls should not be used to compensate for poor
system design. When the controls are slow to respond, the compressors
are either too large for the event or there is insufficient storage.
The ability to
accurately hold set points in the controller will influence the
differential between the load pressures of each compressor. This
differential will determine how far into draw down a compressor must go
before the next compressor loads or is influenced by the signal. It will
also determine the lowest pressure which results in the system at the
highest demand volume.
As an example, if a
system contains a pressure switch that drifts up to 3 psig, and four
compressors - each with a 10 psig dead band - there would be 10 psig for
the first base load unit and at least 3 psig for each additional
compressor, or more than 16 psig across the entire volumetric capacity
of the compressors. Using less than 3 psid between load pressures means
that the inherent drift in the controller could cause the compressors to
fight each other, Fig. 6.

Another consequence
of too high a differential between load set points is that as more
volume is required and the pressure drops, all of the base-loaded
compressors will pump their capacity at lower pressures. Depending on
where the dead bands are relative to optimum performance, this can mean
considerable loss of mass per kilowatt for all units that are on. There
have been systems where the setup of the dead bands was so inappropriate
that the base load capacity would drop faster than the trim compressors
could add capacity. The result was an inability to hold pressure on
larger events. In this case, there was enough capacity, but the setup
used gave the appearance of insufficient supply.
The accuracy of the
pressure signal will also influence the results. Microprocessor controls
receive an electronic signal from a pressure transducer. Most
manufacturers use 62% accuracy; if the transducer is rated at 0 to 200
psig, there can be a 64 psig error across the range of use. This could
cause erratic loading of an additional compressor - or make it difficult
to operate a compressor or the whole system.
With centrifugals,
the signal problem can cause hunting of the inlet and blow off control
valves as well as difficulty with more than one machine. Consequently,
the use of more accurate devices is strongly encouraged. In higher
pressure compressors, the accuracy of the control signal and receiver
becomes more important. Improved accuracy costs more money, but it is
insignificant compared to the demand and usage electric charges of
operating with an extra compressor.
Reprinted
with permission from R. Scot Foss, president of Plant Air Technology,
Charlotte, N.C., a company specializing in system auditing and design. This
article is based on his book, "Compressed Air System Solution."
A
portion of the proceeds from sales of the book is donated to children’s
charities. To order a
copy of the book, please
contact Southern Corporation. |