|
Compressed
Air
Controls
General Control Concepts - Part 1
By R. Scot Foss
President, Plant Air Technology
Key Concepts:
- Control
systems are defined by their application
- Many
compressor controls protect the compressor
- Peak shaving
means only operating needed compressors
When most people
think of compressed air controls, they automatically think of compressor
controls that govern the results in the system. If the system doesn’t
work, whatever that means, more sophisticated controls are normally
recommended. There is at least a chance that this will work. On the
other hand, solutions without problem definitions typically do not
succeed.
Compressed Air System Controls:
Control systems can
generally be defined by their application.
Point of use
– This typically refers to proportional regulators, which restrict flow
and control pressure at a single use point. Regulators are subject to
hysteresis or fluctuation when the application changes flow
requirements. Sometimes flow controls are applied downstream to limit
flow at variable pressure.
Although 75% of most
applications, by point of use count, may have regulators, it is seldom
that more than 50% of most systems volumetric demand is actually
regulated. This is a result of unregulated usage and regulators that are
adjusted to be wide open.
Intermediate or system demand
controllers or expanders
- These are typically applied at one location between supply and demand.
Sometimes they are applied in various user sectors, when there is
sufficient difference in group use pressure to effect a total demand
usage reduction. The intent of this type of controller is to limit the
pressure or density (pressure and temperature) of the downstream users
to a maximum value which is less than that of the minimum supply.
In 98% of the cases,
it is not practical to expect that all production operators will use
their point-of-use controls in the best interests of the system.
System demand
controls separate demand from supply, allowing each to be managed
independently. By doing this, the storage of potential energy on the
supply side is used to reduce on-board energy in an operating pressure
range, while maintaining the lowest constant demand pressure or
pressures simultaneously.
Individual compressor controls
- Because an air compressor is little more than an air pump, air
compressor controls limit performance. This is typically performed by:
·
Throttling or closing the inlet
·
Blowing off a portion or all of the air, usually in conjunction with
inlet limiting devices
·
Closing the discharge and pumping in and out of the inlet
·
Using clearance pockets
·
Throttling the driver in response to a pressure input

Fig. 1.
| |
Demand
expanders control pressure or density of the user’s air supply to a
value less than that contained in a receiver |
|
These individual
control approaches are done in conjunction with either maintaining a
specific pressure or keeping the compressor operating between two
pressures in an operating dead band.
By adjusting
individual controls on a limited number of compressors, the loading and
unloading of compressors can be organized sequentially. The more
compressors there are the wider the required operating pressure ranges.
In most cases,
controls are either set at the same value or overlap each other, causing
all units to be partially loaded to limit the impact of pressure
fluctuation on demand.
Compressor
manufacturers use controls to protect or limit the performance of the
compressor and protect the units and their prime movers. When the
operating parameters of the compressor are out of the boundaries
predetermined by the factory, the controls, operation will protect the
compressor as a priority over the system’s needs.
Most operators have
no knowledge of these pre-developed and adjusted boundaries. Because of
this, it is often difficult to determine whether one or more than one
compressor is operating in a protective mode or working for the system’s
needs.
Multiple compressor controls
- The intent of this type of control is to coordinate the application of
more than one compressor within a range of intended pressures. There are
several types of these controls and many operating protocols or
approaches.
·
Pressure-only controls
- The approach is to keep those compressors, that
are operating, maintaining a pressure or set of pressures. As the demand
changes, the pressure-only control system adds, maintains, or deletes
compressor capacity using available onboard energy to maintain a
pressure or pressures.
There are a number
of subcategories of this type of control. One is sequential
pressure-only control, where the addition or deletion of units is based
on a preset sequence. Typically, the sequence may be rotated in an
orderly manner. This type of control requires an operating pressure
range.
·
Pressure-only load sharing or shedding
- This system utilizes the
application of part-loading throttle controls to maintain all
compressors that need to be on in the same condition of modulation at a
particular pressure. If the pressure changes, capacity controls are used
to return to the original pressure. Load shedding has a load and unload
element to the approach.
· Pressure and time controls
- These are the same as pressure-only
controls, but they add the element of adjustable time delay to the
operation of the logic. The time delay is typically applied to the end
of an unload cycle, restricting reload. This can be tricky to apply
because a time delay can effect pressure as an added protocol. Without
thoroughly evaluating both capacitance and measured events, it can be
easy to make mistakes in adjustment of this type of control system.
·
Rate of change, pressure, and time
- In this format, the difference
between supply and demand is measured in terms of mass or volume. If
supply equals demand, the pressure is stable, which is referred to as a
"zero" rate of change. When supply exceeds demand, there is a positive
rate of change. The reverse would be a negative rate of change. This is
by far the most sophisticated approach, because the precise requirement
for addition or deletion of air and energy is measured.
Example:
If supply is producing a 1000 scfm rate of flow and demand is taking
1200 scfm rate of flow, there is a -200 scfm rate of change. With this
information, pressure values can be used to determine how much time is
needed to reach a minimum or maximum value.
This format can be
operated in a sequence, adding or deleting the next or last compressor
respectively. With this improved cueing data, a selective rate of change
approach can be used, adding or deleting the most appropriate
compressor.
Note:
Some multiple-unit control systems actually control the compressors,
while others enable the compressors. By enabling, the controls select a
compressor and allow it to operate on its independent control and signal
relative to the system. Correspondingly, the central supply control can
block the compressor’s local controls from functioning.
Another common spin
on operating these simple control approaches uses a load and unload set
point inside the local compressor control set points. This is an
extremely simple approach to multiple-compressor controls. It does not
require an integrated interface with the compressor that is controlled
by the outer set points on the compressor’s pressure switch.
·
Peak shaving control - These are very much like the electrical approach
and set up a separate air system off the main system. This peak shaving
system typically operates at a much higher pressure with the intent of
filling a large storage capacitance over time. It then can be fed into
the main system either upstream or downstream of the demand control or
expander to act as a compressor, a support system during a base load
failure while the backup compressor is being loaded into the system, or
as a trim out for high, large events.
An example of this
would be a 10-hp compressor/dryer delivering 40 scfm of air into a
20,000-gal. tank (184 scf/psi) until the tank pressure reaches 200 psig.
When appropriate, this provides a controlled feed from the peak shaving
system, into the main system, down to the demand pressure. If the demand
pressure is 100 psig, there are 18,400 scf, which could be displaced
from peak shaving. It would be displaced at a rate of 1000 scfm for 18.4
min., 3000 scfm for 6.13 min., or 6000 scfm for 3.06 min. It will take
460 min. to refill the 20,000-gal. tank with this 10-hp peak shaving
arrangement.
Peak shaving is not
a complex format. The various approaches to getting the higher pressure,
higher rate of airflow into the main system without upsetting the host
system is the key to this highly applicable systems control approach.
Peak shaving can
prevent operating more compressors than are needed all of the time to
support a large rate-of-change event that appears once in a while for a
limited period of time.
Most systems have at
least one more compressor on than is needed all of the time because the
last time a base compressor failed, the production system failed.
What was the
problem? The pressure dropped quicker than the backup compressor could
be loaded to replace the failure. The problem was negative rate of
change verses time. The solution was to run only the supply compressors
needed to support normal demand and introduce peak shaving instantly to
buy time on a base failure.
If supporting a
large or coincidental event that occurs once an hour or more, there are
60 min. of recovery time. If covering a once-a-shift event, 480 min. of
recovery would be needed.
The idea is that the
more recovery time available, the smaller the peak shaving compressor
system. Remember that a peak shaving compressor will run continuously. A
10-hp compressor and dryer applied with adequate storage and a control
system can act like a 1000-hp compressor for a limited period of time.
These are the
various control approaches that can be used in a compressed air system.
The system must be known quantitatively in order to apply controls that
would include base and trim requirements for each major load condition
including, but not limited to, shifts and weekends.
To make this
quantitative analysis, obtain the order of events that occur in the
system in terms of rate of flow, volume per event, duration of the
event, and recovery time available between events. Then measure the
capacitance of the system including all vessels and piping that is
2.5-in. and larger.
The reason for not measuring 2-in. pipes and
smaller is because there is so little storage it is hardly worth
measuring. 1,000-ft of 2-in. pipe is equal to 1.61 scf/psi or less than
100 gal. of storage. Without a demand profile and current capacitance,
the selection of the size and type of compressors and approach to
compressor controls is pure guesswork.
Reprinted
with permission from R. Scot Foss, president of Plant Air Technology,
Charlotte, N.C., a company specializing in system auditing and design. This
article is based on his book, "Compressed Air System Solution."
A
portion of the proceeds from sales of the book is donated to children’s
charities. To order a
copy of the book, please
contact Southern Corporation. |